Produits

Controleur Gantner QBloxx

Le produit

Description

Q.gate IP / DP

Q.gate

 
  • Connection of up to 32 Q.bloxx modules
  • via 2 UARTS, Baud rate up to 24 MBaud each UART
  • Recording of up to 256 variables
  • real format 4 Byte
  • Synchronization and time stamp of measurement values
  • Ethernet interface for configuration and data output
  • FTP, TCP/IP, UDP
  • FTP Server and FTP Client functionality
  • configurable function
  • Optional fieldbus interface
  • Profibus-DP, 12 Mbps
  • High data rate over Ethernet
  • 128 real variables with 1 kHz (block transfer)
    16 real variables with 10 kHz (block transfer)
    64 real variables with 300 Hz (online)
  • Data buffer memory 12 MByte
  • Data buffer at block transfer of measurements
  • Mathematic, control and combination features
  • PAC functionality with extensive function block library
  • Sequences, data logger, PID-controller, transfer functions, mathematic, numeric, Boolean combinations, functions generator
  • Galvanic isolation
  • of power supply and interfaces
  • Electromagnetic Compatibility
  • according EN 61000-4 and EN 55011
  • Power supply 10…30 VDC
  • DIN rail mounting (EN 50022)

up to table ↑
 

 

Q.pac DL / EC

Q.gate

 
  • Connection of up to 32 Q.bloxx modules
  • via 4 UARTS, Baud rate up to 24 MBaud each UART
  • Recording of up to 256 variables
  • real Format 4 Byte
  • Synchronization and time stamp of measurement values
  • Ethernet interface for configuration and data output
  • FTP, TCP/IP, UDP
  • FTP Server and FTP Client functionality
  • configurable function
  • Optional fieldbus interface
  • EtherCAT according specification ETG
  • High data rate over Ethernet
  • 128 real variables with 1 kHz (block transfer)
    16 real variables with 10 kHz (block transfer)
    64 real variables with 300 Hz (online)
  • Data buffer memory dyn. 12 MByte, stat. 128 MByte
  • Data buffer at block transfer of measurements
  • PAC functionality with extensive function block library
  • Sequences, data logger, PID-controller, transfer functions, mathematic, numeric, Boolean combinations, functions generator
  • Galvanic isolation
  • of power supply and interfaces
  • Electromagnetic Compatibility
  • according EN 61000-4 and EN 55011
  • Power supply 10…30 VDC
  • DIN rail mounting (EN 50022)

up to table ↑


  

Q.station

Q.Station

 
  • Very high data rates up to 100 kHz
    each channel
  • 100 kHz at 16 channels, 10 kHz at 128 channels
  • 64 Q.bloxx modules connectable
  • Ethernet interface for configuration
    and data output
  • 1 Gig-E, TCP/IP, UDP, up to 16 MB/s
    Modbus TCP/IP, ASCII, High Speed Port
    Web-server, web client and e-mail
  • Fieldbus interface
  • EtherCAT-Slave, 256 variables read and write
    at 10 kHz 2 x CAN, 2 x USB 2.0, 4 MB/s
  • Synchronization and time stamp
    of measurement values
  • IRIG 2 based master slave principle on RS485 standard system synchronization ±1 ìs applicable
  • Data buffer memory dyn. 500 MByte, stat. 4 GByte
  • expandable over USB (up to 1000000 measurements/s) and SD card
  • PAC functionality with extensive function block library
  • fast PID-controller, sequences, data logger, transfer functions, mathematic, numeric, Boolean combinations, functions generator
  • 8 digital I/O
  • direct connection of encoder for fast angle measurement frequency, PWM and counter measurements, state signals
  • Display (optional)
  • 3.5” full VGA 480 x 640 dots
    capacitive touch screen, programmable content
    VNC support

up to table

Avantages

Le + produit

L’ajout d’un contrôleur transforme les modules Q.bloxx en un puissant système d’automatisation et de contrôle de test

Le contrôleur est l’interface entre les modules Q.bloxx et le système d’automatisation, et gère la synchronisation, la mise en mémoire tampon de données, le contrôle-commande, et le transfert des données vers le système d’automatisation (typiquement sur un PC). L’exigence des différentes applications (nombre de mesures, fréquence, programmation, contrôle, etc) définiront le type de contrôleur à utiliser. Une connexion Ethernet TCP / IP pour la configuration de l’ensemble du système de mesure (y compris le Q. bloxxs), et pour l’acquisition de données de base et les tâches de transfert.

Votre besoin est unique

Demande produit personnalisée

  • Ce champ n’est utilisé qu’à des fins de validation et devrait rester inchangé.

Demande de devis

  • Hidden
  • Ce champ n’est utilisé qu’à des fins de validation et devrait rester inchangé.

Découvrez notre dernier catalogue !

  • Ce champ n’est utilisé qu’à des fins de validation et devrait rester inchangé.

Découvrez notre catalogue fibre !

  • Ce champ n’est utilisé qu’à des fins de validation et devrait rester inchangé.